1 · Input data
Design check of a rectangular tied column under factored axial compression and moment about one principal axis, to ACI CODE-318-25 (procedure ENG-2026-10-028): the material and dimensional limits, the longitudinal reinforcement limits, the slenderness test and, where it is needed, the moment magnification of 6.6.4; the axial cap of Table 22.4.2.1; the strength reduction factor φ from Table 21.2.2 with the new 21.2.2.3 cap; the P–M interaction diagram by strain compatibility about the plastic centroid; the design check of 10.5.1.1; and the detailing of ties, lateral support, spacing, cover and compression lap splices. Every parameter below is required. Press Solve the column check when the card is complete — if anything is missing or malformed the page opens a pop-up naming each parameter and computes nothing; an input that is well-formed but outside the procedure is refused with the clause that refuses it.
Section and materials
Longitudinal reinforcement Ast
Ties
Factored forces
Slenderness and framing
Concrete and aggregate
—
2 · Solution
No solution yet — complete every input in the card above and press Solve the column check. This card stays empty until a solution is computed, and it is emptied again the moment any input changes, so a displayed solution always belongs to the inputs on screen.